Product

DGL2-125

DGL2-125 series residual current circuit breaker (hereinafter referred to as the circuit breaker) is mainly used in AC 50Hz circuit with rated voltage 400V and rated current up to 125A. In case of personal electric shock or when the grid leakage exceeds the specified value, the residual current circuit breaker can quickly cut off the power supply in a very short time for protection of the safety of people and electrical equipment and also for infrequent changeover of line and infrequent start of motor. This product is suitable for various places such as industry, business, and high-rise residential buildings

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGEnterprise code
L2Magnetic type residual current circuit breaker
125Frame rated current (A)
2PNumber of poles: 2P/ 4P
Awave form type: A/AC/G/S/F
40Rated current (A) 16,20,25,32 40,50,63,80,100,125
30mARated residual action current (mA)
DGL2-125

Wiring diagram


Product and installation dimensions(MM)


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGL2-125 series, such as: DGL2-125 residual current operated circuit breaker
  • Number of poles of product, such as 2P
  • Rated current, such as 32A
  • Rated residual operating current, such as: 30mA
  • type wave form of earth leakage sensed such as: A type
  • Order quantity, such as: 1000 units
  • Specified as: DGL2 -125 32A 2P 30mA AC type 1000 units


Inquiry

    Technical Data

    Product nameDGL2-63DGL2-125
    StandardsIEC61008-1IEC61008-1
    CertificateKema CE, CBKema CE, CB
    Electrical characteristics
    Number of poles2P/4P2P/4P
    Rated frequency (Hz)50/6050/60
    Frame current (A)Inm63125
    Rated current (A)In16,20,25,32,40,50,6380,100,125
    Rated voltage (V)AC240V/415V  (230V/400V)AC240V/415V  (230V/400V)
    Rated insulation voltage (V)Ui500500
    Rated impulse withstand voltage (kV)Uimp44
    Rated short-circuit breaking capacity (kA)Ics7.57.5
    Rated short-circuit breaking capacity (kA)Icn1010
    Trip formLeakage tripLeakage trip
    Pollution level22
    Rated residual action current (mA)30100/30030100/300
    Max. breaking time at the rated residual current0.1s0.1s
    wave form of earth leakage sensedAC / A / G / S / FAC / A / G / S / F
    Mechanical properties
    Electrical life60006000
    Mechanical life1000010000
    Protection gradeIP20IP20
    Indicator windowContact status indicationContact status indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃-35℃ ~ +70℃
    Installation site altitude≤ 2000m≤ 2000m
    TerminalsFixed with screwFixed with screw
    Maximum wiring capacity25mm250mm2
    Maximum limit torque Nm3.53.5
    Installation categoryClass Ⅱ , ⅢClass Ⅱ , Ⅲ
    Installation method35mm standard rail35mm standard rail
    Incoming methodUpper and lowerUpper and lower
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    61.5
    102.5
    16, 204
    256
    3210
    40, 5016
    6325
    80,100,12550
    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002