Product

DGB3-40E

DGB3-40E Miniature Circuit Breakers with 4.5KA breaking capacity was designed to provide protection against short circuit and overload for domestic,commercial and industrial electrical installations

 

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB3Enterprise code
40E 4.5KA/6KAFrame rated current (A) E :6ka,no mark :4.5ka
1P+CNumber of poles: 1P+N
CInstantaneous Trip characteristic type: B, C
40Rated current (A) 6,10,16,20,25,32,40
DGB3-40E

Tripping Characteristic Curves

IEC60898- 1


Product and installation dimensions(MM)

DGB3-40E should be installed on DIN rail terminal and can be connected to the wire less than 16mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB3-40E series miniature circuit breaker, breaking capacity 10kA, C-type instantaneous
  • release, rated current 32A, two-pole, 1000
  • Specified as: DGB3-40E C32 2P 1000 units


Inquiry

    Technical Data

    Product nameDGB3-40DGB3-40E
    StandardsIEC60898- 1IEC60898- 1
    CertificateCE,CBCE,CB
    Electrical characteristics
    Number of poles1P+N1P+N
    Rated frequency (Hz)50/6050/60
    Frame current (A)Inm4040
    Rated current (A)In6,10,16,20,25,32,406,10,16,20,25,32,40
    Rated voltage (V)AC230/400AC230/400
    Rated insulation voltage (V)Ui690690
    Rated impulse withstand voltage (kV)Uimp44
    Rated short-circuit breaking capacity (kA)Ics4.56
    Rated short-circuit breaking capacity (kA)Icn4.56
    Instantaneous trip characteristicsB,CB,C
    Trip formThermal magnetic tripThermal magnetic trip
    Pollution level22
    Mechanical properties
    Electrical life1000010000
    Mechanical life2000020000
    Protection gradeIP20IP20
    Indicator windowContact status indicationContact status indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃-35℃ ~ +70℃
    Installation site altitude≤ 2000m≤ 2000m
    TerminalsFixed with screwFixed with screw
    Maximum wiring capacity16mm216mm2
    Maximum limit torque Nm2.52.5
    Installation categoryClass Ⅱ , ⅢClass Ⅱ , Ⅲ
    Installation method35mm standard rail35mm standard rail
    Incoming methodUpper and lowerUpper and lower
    Action performance of circuit breaker
     Rated currentStart stateSpecified timeExpected resultsRemarks 
     

     

     

    Thermal Release

    6-40ACold state1.13 Int ≤ 1hNot trip 
     

    6-40A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    ≤32 

    Cold state

     

    2.55 In

    1s < t < 60sTrip 
    >321s < t < 120sTrip 
     

     

     

    Magnetic Release

     

     

    6-40A

     

     

    Cold state

    3In(B type) 

     

    t ≤ 0. 1s

     

     

    Not trip

     

    “Turn on the auxiliary switch

    for making current”

    5In (C type)
    10In(D type)
     

     

    6-40A

     

     

    Cold state

    5In(B type) 

     

    t < 0. 1s

     

     

    Trip

    “Turn on the auxiliary switch

    for making current”

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 2N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    1, 2, 3, 4, 5, 61.5
    102.5
    16, 204
    256
    3210
    4016

     