Product

DGB8-63

DGB8-63 Miniature Circuit Breakers with 4.5KA/6kA breaking capacity was designed to provide protection against short circuit and overload for domestic,commercial and industrial electrical installations.

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB8Enterprise code
63Breaking capacity 4.5kA/6kA Frame rated current (A)
1PNumber of poles: 1P, 2P, 3P, 4P
CInstantaneous Trip characteristic type: B, C, D
40Rated current (A) 1,2,3,4,5,6,10,16 ,20,25,32,40,50, 63
OF2accessories MX2/OF2/SD2 MV+MN2
DGB8-63

Tripping Characteristic Curves

IEC 60898-1


Product and installation dimensions(MM)

DGB3-63E should be installed on DIN rail terminal and can be connected to the wire less than 25mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order  quantity of the instantaneous release when ordering.
  • Order example: DGB8 series miniature circuit breaker, breaking capacity 6kA, C-type instantaneous
  • release, rated current 32A, two-pole, 1000
  • Specified as: DGB8-63 C32 2P 1000 units


Inquiry

    Technical Data

    Product nameDGB8-63
    StandardsIEC60898- 1
    CertificateCE, CB
    Electrical characteristics
    Number of poles1P,2P,3P,4P
    Rated frequency (Hz)50/60
    Frame current (A) Inm63
    Rated current (A) In1,2,3,4,5,6,10,16,20,25,32,40,50,63
    Rated voltage (V)AC230/400(1P) AC400(2P,3P,4P)
    Rated insulation voltage (V) Ui690
    Rated impulse withstand voltage (kV)Uimp4
    Rated short-circuit breaking capacity (kA)Ics4.5 / 6
    Rated short-circuit breaking capacity (kA)Icn4.5 / 6
    Instantaneous trip characteristicsB,C,D
    Trip formThermal magnetic trip
    Pollution level2
    Electrical and mechanical accessoriesMV+MN2 (overvoltage and undervoltage), OF2 (auxiliary), SD2 (alarm), MX2 (shunt)
    Mechanical properties
    Electrical life10000
    Mechanical life20000
    Protection gradeIP20
    Indicator windowContact status indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃
    Installation site altitude≤ 2000m
    TerminalsFixed with screw
    Maximum wiring capacity25mm2
    Maximum limit torque Nm2.5
    Installation categoryClass Ⅱ , Ⅲ
    Installation method35mm standard rail
    Incoming methodUpper and lower
    Action performance of circuit breaker
     Rated currentStart stateSpecified timeExpected resultsRemarks 
     

     

     

    Thermal Release

    1-63ACold state1.13 Int ≤ 1hNot trip 
     

    1-63A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    ≤32 

    Cold state

     

    2.55 In

    1s < t < 60sTrip 
    >321s < t < 120sTrip 
     

     

     

    Magnetic Release

     

     

    1-63A

     

     

    Cold state

    3In(B type) 

     

    t ≤ 0. 1s

     

     

    Not trip

     

    “Turn on the auxiliary switch

    for making current”

    5In (C type)
    10In(D type)
     

     

    1-63A

     

     

    Cold state

    5In(B type) 

     

    t < 0. 1s

     

     

    Trip

    “Turn on the auxiliary switch

    for making current”

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    1, 2, 3, 4, 5, 61
    101.5
    16, 202.5
    254
    326
    40, 5016
    6325

     

    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002