Product

DGB3-63E

DGB3-63/DGB3-63E Miniature Circuit Breakers with 4.5KA/6kA breaking capacity was designed to provide protection against short circuit and overload for domestic,commercial and industrial electrical installations

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB3Enterprise code
63EBreaking capacity C: 4.5kA No mark: 6kA Frame rated current (A)
1PNumber of poles: 1P, 2P, 3P, 4P
CInstantaneous Trip characteristic type: B, C, D
40Rated current (A) 1,2,4,5,6,10,16,20 ,25,32,40,50,63
OF2accessories MX2/OF2/SD2 MV+MN2
DGB3-63E

Tripping Characteristic Curves

IEC 60898-1


Product and installation dimensions(MM)

DGB3-63E should be installed on DIN rail terminal and can be connected to the wire less than 25mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB3(E) series miniature circuit breaker, breaking capacity 6kA, C-type instantaneous
  • release, rated current 32A, two-pole, 1000
  • Specified as: DGB3E-63 C32 2P 1000 units


Inquiry

    Technical Data

    Product nameDGB3-63DGB3-63E
    StandardsIEC60898-1IEC60898-1
    CertificateCE, CBCE, CB
    Electrical characteristics
    Number of poles1P,2P,3P,4P1P,2P,3P,4P
    Rated frequency (Hz)50/6050/60
    Frame current (A) Inm6363
    Rated current (A) In1,2,4,5,6,10,16,20,25,32,40,50,631,2,4,5,6,10,16,20,25,32,40,50,63
    Rated voltage (V)AC240V/415V  (230V/400V)AC240V/415V  (230V/400V)
    Rated insulation voltage (V) Ui690690
    Rated impulse withstand voltage (kV)Uimp44
    Rated short-circuit breaking capacity (kA)Ics64.5
    Rated short-circuit breaking capacity (kA)Icn64.5
    Instantaneous trip characteristicsB,C,DB,C,D
    Trip formThermal magnetic tripThermal magnetic trip
    Pollution level22
     

    Electrical and mechanical accessories

    MV+MN2 (overvoltage and undervoltage),

    OF2 (auxiliary), SD2 (alarm), MX2 (shunt)

    MV+MN2 (overvoltage and undervoltage),

    OF2 (auxiliary), SD2 (alarm), MX2 (shunt)

    Mechanical properties
    Electrical life1000010000
    Mechanical life2000020000
    Protection gradeIP20IP20
    Indicator windowContact status indicationContact status indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃-35℃ ~ +70℃
    Installation site altitude≤ 2000m≤ 2000m
    TerminalsFixed with screwFixed with screw
    Maximum wiring capacity25mm225mm2
    Maximum limit torque Nm2.52.5
    Installation categoryClass Ⅱ , ⅢClass Ⅱ , Ⅲ
    Installation method35mm standard rail35mm standard rail
    Incoming methodUpper and lowerUpper and lower
    Action performance of circuit breaker
     Rated currentStart stateSpecified timeExpected resultsRemarks 
     

     

     

    Thermal Release

    1-63ACold state1.13 Int ≤ 1hNot trip 
     

    1-63A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    ≤32 

    Cold state

     

    2.55 In

    1s < t < 60sTrip 
    >321s < t < 120sTrip 
     

     

     

    Magnetic Release

     

     

    1-63A

     

     

    Cold state

    3In(B type) 

     

    t ≤ 0. 1s

     

     

    Not trip

     

    “Turn on the auxiliary switch

    for making current”

    5In (C type)
    10In(D type)
     

     

    1-63A

     

     

    Cold state

    5In(B type) 

     

    t < 0. 1s

     

     

    Trip

    “Turn on the auxiliary switch

    for making current”

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    61.5
    102.5
    16, 204
    256
    3210
    40, 5016
    6325

     

    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002