Product

DGB1-63HS

DGB1-63HS Miniature Circuit Breakers with 6KA breaking capacity was designed to provide protection against short circuit and overload for domestic,commercial and industrial electrical installations

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB1Enterprise code
63HSFrame rated current (A) & design Code
1PNumber of poles: 1P, 2P, 3P, 4P
CInstantaneous Trip characteristic type: B, C, D, CK, K
40Rated current (A) 1,2,4,5,6,10,16,20 25,32,40,50,63
OF2accessories MX2/OF2/SD2 MV+MN2
DGB1-63HS

Tripping Characteristic Curves

IEC 60898-1


Product and installation dimensions(MM)

DGB1-63HS should be installed on DIN rail terminal and can be connected to the wire less than 25mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB1-63HS series miniature circuit breaker, breaking capacity 6kA, C-type instantaneous
  • release, rated current 32A, two-pole, 1000
  • Specified as: DGB1-63HS C32 2P 1000 units


Inquiry

    Technical Data

    Product nameDGB1-63HS
    StandardsIEC60898- 1
    CertificateCE, SEMKO, CB
    Electrical characteristics
    Number of poles1P,2P,3P,4P
    Rated frequency (Hz)50/60
    Frame current (A) Inm63
    Rated current (A) In1,2,4,5,6,10,16,20,25,32,40,50,63
    Rated voltage (V)AC240V/415V  (230V/400V)
    Rated insulation voltage (V) Ui690
    Rated impulse withstand voltage (kV)Uimp4
    Rated short-circuit breaking capacity (kA)Ics6
    Rated short-circuit breaking capacity (kA)Icn6
    Instantaneous trip characteristicsB,C,D
    Trip formThermal magnetic trip
    Pollution level2
    Electrical and mechanical accessoriesMV+MN2 (overvoltage and undervoltage), OF2 (auxiliary), SD2 (alarm), MX2 (shunt)
    Mechanical properties
    Electrical life10000
    Mechanical life20000
    Protection gradeIP20
    Indicator windowContact status indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃
    Installation site altitude≤ 2000m
    TerminalsFixed with screw
    Maximum wiring capacity25mm2
    Maximum limit torque Nm2.5
    Installation categoryClass Ⅱ , Ⅲ
    Installation method35mm standard rail
    Incoming methodUpper and lower
    Action performance of circuit breaker
     Rated currentStart stateSpecified timeExpected resultsRemarks 
     

     

     

    Thermal Release

    1-63ACold state1.13 Int ≤ 1hNot trip 
     

    1-63A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    ≤32 

    Cold state

     

    2.55 In

    1s < t < 60sTrip 
    >321s < t < 120sTrip 
     

     

     

    Magnetic Release

     

     

    1-63A

     

     

    Cold state

    3In(B type) 

     

    t ≤ 0. 1s

     

     

    Not trip

     

    “Turn on the auxiliary switch

    for making current”

    5In (C type)
    10In(D type)
     

     

    1-63A

     

     

    Cold state

    5In(B type) 

     

    t < 0. 1s

     

     

    Trip

    “Turn on the auxiliary switch

    for making current”

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    61.5
    102.5
    16, 204
    256
    3210
    40, 5016
    6325

     