Product

DGB1NLE-63HS

DGB1NLE-63HS series residual current circuit breaker with overcurrent protection is mainly used in AC 50Hz with rated working voltage 230V and with rated current up to 63A. In case of personal electric shock or when the grid leakage current exceeds the specified value, the residual current action circuit breaker can work to quickly cut off the power supply within the very short time for protection of the safety of personnel and electrical equipment as infrequent conversion of the line under the overload, short-circuit, overvoltage and normal situations, especially suitable for industrial and business lighting power distribution system.

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB1Enterprise code
NLEElectronic type residual current circuit breaker
63HSFrame rated current (A) HS: design code
1P+NNumber of poles: 1P+N
CInstantaneous Trip characteristic type: B, C, D
40Rated current (A) 6,10,16,20,25,32,40,50,63
30mARated residual action current (mA)
DGB1NLE-63HS

Tripping Characteristic Curves

IEC 61009-1/IEC61008-1


Product and installation dimensions(MM)

DGB1NLE-63HS should be installed on DIN rail terminal and can be connected to the wire less than 25mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB1NLE-63HS series, such as: DGB1NLE-63HS residual current operated circuit breaker
  • Trip type, such as: C type
  • Number of poles of product, such as 1P+N
  • Rated current, such as 32A
  • Rated residual operating current, such as: 30mA
  • type wave form of earth leakage sensed such as: A type
  • Order quantity, such as: 1000 units
  • Specified as: DGB1NLE-63HS C32 1P+N 30mA A type 1000 units


Inquiry

    Technical Data

    Product nameDGB1NLE-63HS (Electronic)DGB1NL-63HS (ELectromagnetic)
    StandardsIEC61009-1IEC61008-1
    CertificateCE, CBCE,CCC,CB
    Electrical characteristics
    Number of poles1P+N1P+N
    Rated frequency (Hz)50/6050/60
    Frame current (A)Inm6363
    Rated current (A)In6,10,16,20,25,32,40,50,636,10,16,20,25,32,40,50,63
    Rated voltage (V)AC230AC230
    Rated insulation voltage (V)Ui500500
    Rated impulse withstand voltage (kV)Uimp44
    Rated short-circuit breaking capacity (kA)Ics66
    Rated short-circuit breaking capacity (kA)Icn66
    Instantaneous trip characteristicsB,C,DB,C,D
    Trip formThermal, magnetic and Lekage tripThermal, magnetic and Lekage trip
    Pollution level22
    Rated residual action current (mA)30/50/100/30030/50/100/300
    Max. breaking time at the rated residual current0.1s0.1s
    Wave form of earth leakage sensedAC / AAC / A
    Overvoltage protection: Uvo=280V±5%optional/
     

     

     

    Electrical and mechanical accessories

    MX: Shunt release, OF: Auxiliary contact, SD: Alarm contact,MX+OF: Shunt release + auxiliary contactMV: Overvoltage release

    MN: Undervoltage release MV+MN: Overvoltage and undervoltage release

    MX: Shunt release, OF: Auxiliary contact, SD: Alarm contact,MX+OF: Shunt release + auxiliary contactMV: Overvoltage release

    MN: Undervoltage release MV+MN: Overvoltage and undervoltage release

    Mechanical properties
    Electrical life40006000
    Mechanical life1000020000
    Protection gradeIP20IP20
    Indicator windowContact status indication and Leakage indicationContact status indication and Leakage indication
    Normal operation conditions and installation characteristics
    Storage temperature-35℃ ~ +70℃-35C~ +70C
    Installation site altitude≤ 2000m≤ 2000m
    TerminalsFixed with screwFixed with screw
    Maximum wiring capacity25mm225mm2
    Maximum limit torque Nm3.53.5
    Installation categoryClass Ⅱ , ⅢClass Ⅱ , Ⅲ
    Installation method35mm standard rail35mm standard rail
    Incoming methodUpper and lowerUpper and lower
    Action performance of circuit breaker
     Rated currentStart stateSpecified timeExpected resultsRemarks 
     

     

     

    Thermal Release

    6-63ACold state1.13 Int ≤ 1hNot trip 
     

    6-63A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    6-63A 

    Cold state

     

    2.55 In

    1s < t < 60sTrip 
    6-63A1s < t < 120sTrip 
     

     

     

    Magnetic Release

     

     

    6-63A

     

     

    Cold state

    3In(B type) 

     

    t ≤ 0. 1s

     

     

    Not trip

     

    “Turn on the auxiliary switch

    for making current”

    5In (C type)
    10In(D type)
     

     

    6-63A

     

     

    Cold state

    5In(B type) 

     

    t < 0. 1s

     

     

    Trip

    “Turn on the auxiliary switch

    for making current”

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A)Nominal cross area of copper wire (mm²)
    61.5
    102.5
    16, 204
    256
    3210
    40, 5016
    6325

     

    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002